SMIO expansion modules for SM50xx

SMIO modules are used to increase the number of physical interfaces in IEDs from Scanmatic e.g. SM5049 or SM5059. SMIO-modules are available in different variants, with different physical interfaces, and they make it possible to tailor the system to the specific application.

The following modules are available:

  • SMIO SM7552:
    • 4 x high precision 0 – 20 mA for current measurement.
    • 4 x low precision –5 – +30 V for voltage measurement.
    • Internal temperature.
  • SMIO SM7553:
    • 4 x high precision 0 – 2.500 V for voltage measurement.
    • 4 x low precision –5 – +30 V for voltage measurement.
    • Internal temperature.
  • SMIO SM7554:
    • 2 x high precision 0 – 20 mA current measurement.
    • 2 x high precision half bridge for Aandreaa sensors.
    • 2 x low precision –5 – +30 V voltage measurement.
    • Internal temperature.
  • SMIO SM7555:
    • 12 x isolated digital inputs.
    • Internal temperature.
  • SMIO SM7556:
    • 12 x isolated digital outputs.
    • Internal temperature.
  • SMIO SM7557:
    • 1 x analog RTD measurement.
    • Internal temperature

SMIO modules are connected to the IED via the SMIO bus (RS485). Addressing and identification of the different modules is automatic. Each module has a unique ID detected by the IED. The ID together with module type information makes it possible for the IED to automatically identify the presence of a module on the bus. The physical connection is via a 5 pins bus connector. The number of bus connectors can be increase on demand.